Glossary · 56 entries · the way we use them
A working vocabulary.
Cultural-heritage HVAC sits at the intersection of ASHRAE engineering, conservation science, building physics, and library/archive practice. The vocabularies do not cleanly overlap. Below, the working terms we use in the binders, defined the way we use them.
ASHRAE classes
- Class AA
- 21 °C ±2 / 50% RH ±5, with proofed daily fluctuations of ±2 °C and ±5% RH and no seasonal RH adjustment. The strictest class. See Protocol I.
- Class As
- Same daily fluctuations as AA but allowing seasonal RH adjustment of up to ±10%. The most-deployed class in our practice; energy-favorable; preservation-equivalent for most collections.
- Class Ad
- Same daily fluctuations as AA but allowing seasonal T adjustment (typically 5 °C cooler in winter). Less common; energy-favorable in cold climates.
- Class B
- ±5 °C, ±10% RH daily, with seasonal RH adjustment of ±10%. The class we use for historic retrofits when the building cannot hold A.
- Class C
- RH controlled (typically 25–60%) but T uncontrolled. Suitable for archival paper in dry climates.
- Class D
- RH below 75% only. Equivalent to a dry attic. Acceptable for some metal collections; unacceptable for most paper.
IPI environmental ratings
- NA factor
- Natural Aging factor: a multiplier on the room-temperature aging baseline (NA = 1 at 21 °C/50% RH). NA = 12 means twelve times slower aging. Reported by the IPI Dew Point Calculator.
- MD risk
- Mechanical Decay risk. Driven principally by RH stability rather than RH absolute value. Categorical (low, medium, high).
- MG risk
- Mold Growth risk. Threshold around 60% RH and dwell time. Categorical.
- MC risk
- Metal Corrosion risk. Driven by RH absolute value. Categorical.
- Dew point (DP)
- The temperature to which a parcel of air must be cooled to reach 100% RH and condense out water. Measured in °C. The single most important number in conservation HVAC after RH.
Mechanical & controls
- AHU
- Air-handling unit. The box that conditions air (cooling, reheat, humidification, filtration) and delivers it to the rooms.
- BMS
- Building Management System. The control software that runs the mechanical. We deploy Niagara.
- Cascade
- A two-stage refrigeration scheme used for sub-zero cool storage. The first stage cools the second stage, which cools the room.
- Chiller
- A water-cooled or air-cooled refrigeration unit that produces chilled water for the AHU’s cooling coil. We typically deploy Trane CenTraVac or Daikin Magnitude magnetic-bearing units.
- DOAS
- Dedicated Outside-Air System. Conditions outside air separately from recirculated air, allowing finer humidity control on the make-up.
- ECM blower
- Electronically Commutated Motor blower. Variable-speed, energy-efficient. Standard on our designs.
- ERV
- Energy Recovery Ventilator. A heat-and-moisture exchanger between exhaust air and incoming outside air. Recovers ~78% of the latent and sensible energy that would otherwise be exhausted.
- Iso-steam humidifier
- A humidifier producing isothermal steam (no heating effect on the room). Cleaner than atomized humidification.
- Maglev chiller
- Magnetic-bearing centrifugal chiller. No mechanical bearings, no oil, no friction. Higher partial-load COP. Read more at GSA.
- Plenum
- An air-distribution chamber where pressure is equalized before air is delivered to ducts. Half of the practice’s name.
- Reheat coil
- A coil that warms the cooled air after dehumidification, to deliver it to the room at the right temperature without re-humidifying.
- VRF
- Variable Refrigerant Flow. A multi-zone heat-pump architecture, useful in residential conservation work for its discretion.
Sensors & telemetry
- Burn-in
- The 14-day period in which a new sensor is held at controlled conditions against a reference probe to verify its calibration before deployment.
- Calibration drift
- Slow change in a sensor’s reported value over time, due to component aging. Modern Conserv nodes drift < 0.3 °C over 5 years.
- LoRaWAN
- Long Range Wide-Area Network — a low-power, long-range radio protocol for IoT, operating on unlicensed sub-GHz ISM bands. Penetrates masonry buildings far better than Wi-Fi.
- Reference probe
- A NIST-traceable T/RH probe used to calibrate working sensors. Ours are kept in the sensor lab on the second floor of the shop.
- Ribbon
- A long-form plot of T and RH over time, typically days to years. The single most-read artifact in our practice.
- Setpoint
- The T and RH value the BMS is targeting. Distinct from the actual T and RH the room reaches.
Building physics
- Air change rate (ACH)
- How many times the air in a room is replaced per hour. Measured at 50 Pa pressure differential for envelope tightness.
- Envelope
- The thermal/moisture boundary of a building or room. Walls, windows, roof, floor, doors. The envelope is the system; the chiller is what is in the room because the envelope is not yet good enough.
- Hygrothermal
- Pertaining to combined heat and moisture transport. WUFI is the modeling tool.
- Vapor barrier
- A continuous membrane that prevents water vapor from passing. Placed on the warm side of the insulation in heating-dominated climates.
- Vestibule
- A buffered transition space between the controlled environment and the uncontrolled environment. Conditioned to an intermediate setpoint to prevent moist outside air from entering the vault.
Conservation
- Acclimatization
- The collection’s slow adjustment to a new environment. See equilibration.
- Acetate base
- Cellulose-acetate film base, vulnerable to vinegar-syndrome hydrolysis. Cool-storage candidate.
- Cellulose nitrate
- The first plastic film base, used 1889–1951, fire-hazardous, decomposes via autocatalytic chemistry. Requires sub-zero vented storage. See mixed-media storage.
- Conserve O Gram
- The NPS’s short technical-leaflet series on collection care. Free, online, indispensable.
- Equilibration
- The process by which a collection comes into balance with a new environmental setpoint. Typically 2–18 months. Gate M5 in our method.
- Foxing
- Reddish-brown discoloration on paper, often associated with humidity. A symptom of unstable storage.
- Glass-transition zone
- The thermal range over which a polymer transitions from glassy to rubbery behavior. For glass-plate negatives, the zone is around 11 °C and is a stress-prone region of any cooling ramp.
- Mirroring (silver)
- Surface migration of silver to the emulsion-air interface in silver-gelatin photographs, producing a metallic sheen. A symptom of long-term oxidation.
- Proofed fluctuation
- A daily T or RH fluctuation that has been demonstrated, by direct observation of the room’s behavior, to be sustainable. Distinct from a setpoint specification on a drawing.
- Stop-work event
- An out-of-band excursion that triggers an emergency response per a written stop-work procedure. We have observed approximately 0.4 stop-work events per year per retainer site.
- Vinegar syndrome
- The autocatalytic hydrolysis of cellulose-acetate film base, releasing acetic acid (vinegar smell). Slowed dramatically by cold storage. See Protocol II.
Practice-specific
- Binder
- The hand-bound 60–180-page document delivered to a client at final commissioning. Indexed, signed, working.
- Daybook
- The form in which we file site-walk notes. Borrowed from Aldo Leopold. See winter shutdown walks.
- Gate
- One of the six method gates: M1 walk, M2 risk register, M3 schematic, M4 build, M5 equilibration, M6 standing watch. See protocols page.
- Quiet ramp
- The two-week period at the end of construction during which the system runs to setpoint without the collection in the room.
- Ribbon, signed
- The long-term ribbon that signals Gate M5 closure: the room has held setpoint within band for one full annual cycle.
- Rooms-within-rooms
- The mixed-media compromise scheme: a baseline regime for the room, with smaller dedicated envelopes inside the room for material classes that need a different regime. See mixed-media storage.
- Walk & ribbon
- Gate M1: a two-week instrumented baseline before any design proposal. Sixteen sensors, two walks, an interview with the staff.
Missing a term?
Write studio@plenumandreed.example. The glossary grows by a few entries a quarter.
References
- ASHRAE Handbook — HVAC Applications, Chapter 24. ashrae.org.
- IPI Dew Point Calculator. dpcalc.org.
- NPS Conserve O Gram. nps.gov.
- WUFI hygrothermal modeling. wufi.de.
- Tridium Niagara Framework. tridium.com.
- Conserv environmental monitoring. conserv.io.
- NIST Special Publication 250. nist.gov/calibrations.
- Library of Congress preservation glossary. loc.gov/preservation.